TPI 709 Combustion Analyzer Measure Carbon Monoxide (CO), Carbon Dioxide (CO2), Oxygen (O2)

Thumbnail Filmstrip of TPI 709 Combustion Analyzer Measure Carbon Monoxide (CO), Carbon Dioxide (CO2), Oxygen (O2) Images

    TPI 709 Combustion Analyzer Measure Carbon Monoxide (CO), Carbon Dioxide (CO2), Oxygen (O2)

    Overview

    The TPI 709 Flue Gas Combustion Analyzer is a state of the art, easy to use combustion analyzer. Designed to Measure Carbon Monoxide (CO), Oxygen (02) and Carbon Dioxide (CO2) not only to display and calculate the required readings from a flue but also to cover most of the other measurements associated with combustion.The TPI 709 combustion analyzer uses state of the art electrochemical sensors. This sensor technology provides the longest lasting, most accurate and reliable means for performing combustion tests.
    Features
    • Measure Carbon Monoxide (CO), Oxygen (02) and Carbon Dioxide (CO2)
    • Built-in differential manometer with 0.001" H2O resolution
    • Calculates combustion efficiency
    • Pump driven for fast response
    • Will not shut off if 15 ppm CO is present for increased safety
    • Ten selectable fuels: Natural Gas, LPG, Light Oil, Heavy Oil, Bituminous Coal, Anthracite Coal, Coke, Butane, Wood, Bagasse
    • Optional A740 IR printer available for hard copies of test results
    • Built-in differential thermometer
    • Store function to save up to 50 readings
    • Large easy to read backlit display
    Price Starting At:
    $550.00
    Need help? Contact us with questions.

      Shipping Estimated Shipping 1 to 2 weeks.
    TPI 709 Combustion Efficiency Analyzer Measurement Specifications
    Parameter Range Resolutoin Accuracy
    Carbon Monoxide (CO) 0 to 10,000 ppm 1 ppm ±5ppm or 5% of reading whichever is greater
    Oxygen (02 0 to 25% 0.1% ±0.3%
    Carbon Dioxide (CO2) 0 to 25% 0.1% Calculated Value
    Nitric Oxide Measurement N/A - -
    NOx Measurement N/A - -
    Temperature -40 to 1472°F (-40 to 800°C) 1°F or °C (K-type) ±0.3%, ±2°F or ±1°C
    Draft/Pressure -150 mBar to +150 mBar -15 kPa to +15 kPa -60 inH2O to +60 in H20
    Selectable Ranges mBar, kPa, and inH2O
    0.001 inH2O ±0/5% fsd
    Gross/Net Efficiency 0 to 100% 0.1% Calculated Value
    CO/CO2 Ratio 0 to 0.999 0.001 Calculated Value
    TPI 709 Combustion Efficiency Analyzer General Specifications
    Combustible Gas Level Indication Yes (For flue gasses)
    Operating Temperature 14°F to 122°F (-10°C to 50°C)
    Battery Type 1.5V AA (3)
    Selectable Fuels Natural Gas, LPG, Light Oil, Heavy Oil, Bituminous Coal,
    Anthracite Coal, Coke, Butane, Wood, Bagasse
    Display Type Backlit 3 line LCD
    Data Storage 50 Locations
    Data Logging N/A
    Print Capability Yes, via Optional IR printer (A740)
    PC Communication N/A
    Date and Time Function 24 Hour Real Time Clock
    Dimensions 200mm x 90mm x 60mm
    Weight 500g
    Conformity BS7927 (and the draft BS7967)