S1-RD3 Refrigerant Gas Leak Detector
Overview
Whether testing for leaks in air conditioning, refrigeration, or automotive AC, the versatile Model Si-RD3 Refrigerant Gas Leak Detector spans the diverse needs of technicians, refrigeration engineers, and maintenance personnel around the globe. From freezer coils to heat pumps, experience fast, reliable results that save you both time and money.Features
- Detection includes: all HFCF and HFC refrigerants, R1234yf, R1234ze, R290, R600a, and 5% hydrogen - 95% nitrogen mixtures (Nidron 5, Trace-A-Gas)
- Manual and automatic auto zero. Immediately ready to use with no presets
- Heated diode sensor
- Visible and audible alarms
- 3 modes: Low, Normal and High sensitivity
- 11.8" (30 cm) Length Flexible Goose Neck Probe
- Highly sensitive: 0 to 3 g/year
Applications
- Check for leaks in refrigeration systems
- Test for leaks in air conditioning systems and cooling units
- Find leaks in automotive air conditioning systems
Price Starting At:
$449.00
$449.00
Shipping Estimated Shipping 3 to 5 Business Days
Si-RD3 Refrigerant Gas Leak Detector Specifications
Detected Gases | HFC: R134a, R404a, R407c, R410a, R32, R422a/b/c/d, R425a, R507a, R125 HCFC: R22 CFC: R12, R502 Others: 5% hydrogen - 95% nitrogen (Nidron 5, Trace-A-Gas), R290, R600a, R1234yf, R1234ze |
Measuring Element | Semi-Conductor Sensor |
Display | 13 LEDs: 8 Graphics, 3 Sensitivity, 2 Battery Level & Manual Auto zero |
Indication | LED: Gradually lights up when the gas concentration increases Audible: Beep frequency increases when the gas concentration increases |
Operating Conditions | Temperature 32°F to 122°F (0°C to 50°C) in non-condensing conditions > Altitude 0 to 6,550 ft / 0 to 2,000 m |
Ambient Environment | Neutral Gas |
Goose Neck Length Probe | Flexible, 11.8 in. (30 cm) long |
Case Deminsions | 5.7 in. (147.9 mm) X 2.81 in (71.5mm)g |
Case Housing | ABS topsafe, protection IP54 |
Keypad | 3 Keys |
Autonomy | > 12 Hrs |
Auto Shut-Off | 15 Min |
Battery | 4 AAA LR03 1.5 V Batteries |
Weight | 10.5 oz (295 g) |
Storage Temperature | -4°F to 176°F (-20°C to 80°C) |
European Directives | 2014/30/EU EMC ; 2014/35/EU Low Voltage; 2011/65/eu RoHS II ; 2012/19/EU WEEE |
Si-RD3 Refrigerant Gas Leak Detector Sensitivity
Mode | Indicative measuring range (g/an) | Visual alarm |
---|---|---|
Sensitivity | Low sensitivity ("L" on the device) | From 0 to 300 g/an |
Normal sensitivity "M" on the device | From 0 to 30 g/an | All the leds (8) for 30 g/an |
High sensitivity "H" on the device | From 0 to 3 g/an | All the leds (8) for 3 g/an |